Product guide
Diesel Generator Sets
A diesel generator set is an engine, an alternator and a control panel mounted on a common base frame and rated to a defined duty. This guide covers how the ratings on a datasheet are defined, which power range fits which job, and what has to be in an enquiry before a set can be selected.
Ratings
How a generator set is rated
Two sets with identical hardware carry different numbers depending on the duty they are sold for. ISO 8528-1 defines the four ratings that appear on commercial datasheets.
| Rating | Duty | Overload | Annual hours |
|---|---|---|---|
| ESP — emergency standby | Mains failure only | Not permitted | Up to about 500 h |
| PRP — prime power | Continuous variable load | 10% for 1 h in every 12 h | Unlimited |
| COP — continuous power | Constant load, no variation | Not permitted | Unlimited |
| DCP — data centre power | Variable load, defined step limits | Per manufacturer declaration | Unlimited |
ESP is always quoted higher than PRP for the same machine. If a tender asks for one figure without naming the rating, ask which one it is — the difference is typically 10% of the rating.
Power ranges
Which power range fits which job
| Rating | Typical duty | Usually configured as |
|---|---|---|
| 20–100 kVA | Retail units, telecom cabinets, small offices, villas | Single-phase or three-phase, open frame or small canopy |
| 100–300 kVA | Offices, hotels, clinics, small factories | Three-phase canopy, optional automatic transfer switch |
| 300–800 kVA | Hospitals, production lines, data halls | Three-phase canopy or containerised, parallel-ready control |
| 800–2000 kVA | Data centres, large plants, marine and rental fleets | Containerised or open skid, multi-set parallel configuration |
Pages by power range
Each page carries the rating, the typical specification envelope for the class, the applications it suits and the questions we are asked most often at that size.
-
100 kVA diesel generator
80 kW. Villas, shops, telecom cabinets and borehole pumps.
-
200 kVA diesel generator
160 kW. Hotels, clinics, supermarkets and small workshops.
-
300 kVA diesel generator
240 kW. Hospitals, cold stores and food processing lines.
-
400 kVA diesel generator
320 kW. Facility buses, production lines and small IT rooms.
-
500 kVA diesel generator
400 kW. Hospitals, hotels, data halls and industrial prime power.
-
800 kVA diesel generator
640 kW. Data centres, district cooling, mining and marine duty.
-
1000 kVA diesel generator
800 kW. Technical facilities, airports and oil and gas plants.
-
2000 kVA diesel generator
1600 kW. Campuses, utility duty and heavy industrial plants.
Form factors
Four ways to package the same set
-
Silent canopy
Acoustic enclosure, typically 65–75 dB(A) at 7 m. Standard for hotels, hospitals and residential areas.
-
Containerised
Set, tank and controls inside a 20 ft or 40 ft container with service access doors. Chosen when weather protection, security and long autonomy all matter.
-
Trailer-mounted
Road-towable chassis, used where the set has to move between sites.
-
Open frame
Bare skid-mounted set for plant rooms that already have acoustic treatment and ventilation.
Electrical system
Voltage and frequency combinations
| Voltage | Frequency | Common in |
|---|---|---|
| 400/230 V | 50 Hz | Middle East, Africa, Europe, South Asia |
| 380/220 V | 50 Hz | Older installations and projects written to legacy specifications |
| 415/240 V | 50 Hz | Specifications written to legacy UK standards |
| 440/254 V | 60 Hz | West and Central Africa, legacy Gulf networks |
| 480/277 V | 60 Hz | North American specifications and data centre tenders |
Frequency is set by engine speed — 1500 rpm for 50 Hz and 1800 rpm for 60 Hz — so the frequency must be fixed before the set is built, not adjusted afterwards.
Construction
What is inside the set
| Component | What to check on the datasheet |
|---|---|
| Diesel engine | Make and model, governor type (mechanical or electronic), rated speed, fuel consumption at 50/75/100% load |
| Alternator | Make and model, insulation class, temperature rise, voltage regulation, IEC 60034 rating |
| Control panel | Auto mains failure (AMF) capability, protections, remote monitoring options |
| Base frame and tank | Anti-vibration mounts, base tank capacity, autonomy at full load |
| Cooling and exhaust | Radiator sized for site ambient, silencer type and noise level at 7 m |
| Options | Automatic transfer switch, parallel control, bundled tank, canopy or container, remote monitoring |
Engine makes commonly specified in these power classes include Cummins, Perkins, Volvo Penta, Weichai, Yuchai, Deutz, Kubota, Yanmar and Lovol, paired with brushless alternators such as Stamford, Leroy-Somer or Marathon.
Selection
Five steps from load list to order
-
1. List the loads
Running kW and power factor for each load, plus the starting method of the largest motor.
-
2. Fix the duty rating
ESP, PRP, COP or DCP. This single choice changes every number that follows.
-
3. Fix voltage and frequency
Build the electrical system first — it cannot be changed on site later.
-
4. Confirm site conditions
Ambient temperature, altitude, noise limit, fuel storage and access route.
-
5. Choose form and controls
Canopy, container, trailer or open frame; single set or parallel; ATS or manual.
Questions
Common questions
What is the difference between kVA and kW?
kVA is apparent power and kW is real power; the ratio between them is the power factor of the load. Generator sets are rated at a 0.8 power factor as a convention, so a 500 kVA set is quoted as 400 kW. A load with a lower power factor uses more kVA for the same kW.
How much fuel does a diesel generator use?
Budget roughly 0.24 to 0.27 litres per kWh delivered. A 400 kW set running at 75% load, so about 300 kW, therefore burns in the region of 72 to 81 litres per hour. Part-load running is less efficient per kWh than running near rated load.
Should I choose 1500 rpm or 3000 rpm?
Most 50 Hz sets are 1500 rpm four-pole machines, and most 60 Hz sets are 1800 rpm; those speeds are the standard for continuous duty. Higher-speed sets are smaller and lighter but are generally used for light or portable duty.
What does an automatic transfer switch do?
It watches the mains supply, starts the generator when the mains fails, and transfers the load once the set is at voltage and frequency. Transfer typically happens within 8 to 15 seconds of a mains failure, and it transfers back when the mains returns.
What is derating and when does it apply?
Engine and alternator output both fall when ambient temperature is above 40 °C or the site is above 1000 m altitude. The exact derating curve is declared by the engine and alternator manufacturers, so the site conditions have to be known before the rating is finalised.
How much noise does a silent set make?
A canopy set is normally quoted between 65 and 75 dB(A) at 7 m, depending on the enclosure and the rating. If a tender sets a limit below 65 dB(A), the enclosure has to be specified for it rather than chosen from a catalogue.
Form factors
Pages by form factor
The same rating can be built four ways. Which one you need follows from where the set will stand, who will hear it, and how it will get there.
-
Silent diesel generators
Acoustic canopy builds, dB(A) figures at 7 m, and what quiet costs in space and weight.
-
Containerized diesel generators
ISO container packages with tank, cabling, lighting and fire protection inside the box.
-
Trailer mounted diesel generators
Road chassis, braking classes and set-up procedure for sets that move between sites.
-
Open frame diesel generators
Plant room machines: ventilation, heat rejection, foundations and load steps.
Applications
Pages by application
A data centre, a hospital, a hotel, a construction site and an oil and gas facility each impose a different governing requirement on the same machine.
-
Diesel generators by application
The five applications compared side by side, with the figures that decide each specification.
-
Data centres
N+1 and 2N topologies, load steps into UPS and chiller plant, and fuel autonomy.
-
Hospitals
Life safety and critical supplies, imaging loads and 24 h fuel autonomy.
-
Hotels
Guest comfort on changeover, lift ride-through and facade noise limits.
-
Construction sites
Prime power duty in dust and heat, with a load list that changes weekly.
-
Oil and gas
Unattended packages with area classification, fire and gas protection and telemetry.
Not sure which rating you need?
Send the load list, the site conditions and the frequency. We will reply with the rating and the build options that fit.