A set that has been reliable for years stops at three in the morning, and the first useful question is not “what is broken” but “what changed”. Fault finding on a diesel generator is mostly a matter of order: eliminate the cheap and common causes first, treat the controller as a set of measurements rather than a verdict, and only then open the machine. This page is the order we use when a customer sends us a symptom.
Start from the symptom, not the part
Most of the time spent on a fault is spent on the wrong half of the machine, because a symptom describes behaviour and a part is a guess about cause. A set that will not start and a set that starts and then stops share almost nothing beyond the battery. Write down what the set actually does – does the starter turn, does it fire, does it run and then shut down, does it carry load, does it hold frequency – and the possible causes collapse quickly.
Three cheap observations narrow almost every case: cranking speed, which tells you whether the starting system has energy; exhaust behaviour during and after firing, which separates a fuel problem from an air problem; and the controller log, which records which protection operated, and in what order. A photograph of the panel and of the display page showing the last shutdown is worth more than a page of description.
| What the set does | What is already known | Where to go next |
|---|---|---|
| Nothing happens, no crank | The starting system has no energy or has not been given permission | Battery, charger, start relay, safety interlocks, stop loop |
| Cranks, will not fire | The engine turns, but there is no combustion | Fuel supply and shut-off, air, priming, cold-start aid |
| Fires, then shuts down | It combusts, but a protection operates | Oil pressure, coolant temperature, coolant level, overspeed |
| Runs, will not carry load | Engine and alternator run, the delivery path does not | Breaker setting, ATS, excitation, governor, load balance |
What the control panel is actually telling you
An alarm is a measurement plus a threshold, and the two are worth separating. “Low oil pressure” does not mean the engine has no oil; it means the pressure sender read below a setpoint for longer than a delay. The engine may genuinely be losing pressure, the sender or its wiring may be wrong, or the oil may simply be thin and hot at the moment of shutdown. The first check is always whether the reading matches reality, and the second is whether the setpoint suits this installation at all.
A controller also stores a shutdown code and a snapshot: speed, oil pressure, coolant temperature, battery voltage and the last seconds of run time. That snapshot is the single most useful thing you can send to a service desk, because it separates a sensor from a machine in one page.
| Alarm | What the controller measures | Usual causes | First check |
|---|---|---|---|
| Overcrank / fail to start | Crank attempts or crank time exceeded without reaching run speed | Fuel shut-off closed, air in the fuel, weak batteries, cold-start aid, crank limit set too short | Fuel at the filter head, and battery voltage during crank |
| Low oil pressure | Pressure sender below setpoint with the engine running | Low level, wrong viscosity, blocked filter, worn pump or bearings, faulty sender | Dipstick against the gauge, then the sender and its wiring |
| High coolant temperature | Coolant temperature above setpoint | Low coolant, airlock, blocked radiator core, thermostat, belt, fan, dust | Coolant level cold, radiator face, belt tension and condition |
| Low coolant level | Level switch in the expansion tank or radiator top | A real loss through a leak or head gasket, or a sticking float | Find the loss before topping up, or it will return |
| Overspeed | Engine speed above the setpoint, with a short delay | Governor or actuator, wiring, a fuel or oil path into the intake | Find the cause before any restart; do not simply reset |
| Over and under voltage | Alternator output outside the window | AVR, excitation, sensing leads, a heavy load switching | Measure at the terminals with a meter, not the display alone |
| Overcurrent | Current above setpoint for the delay | Genuine overload, a short, a breaker set too low, single-phasing | Compare running kW against the rating and the load list |
| Low battery voltage | Battery below setpoint while the charger should be working | Charger, aged battery, parasitic load, loose or corroded terminals | Charger output, then a load test on the battery |
| Emergency stop | The stop loop was opened | Someone pressed it, or a loose or damaged stop circuit | Reset, then find why it opened; never bridge the loop |
| Earth fault | Insulation to earth below the threshold | Damp alternator or cabling, damaged cable, a real fault | Insulation test with the set isolated and locked off |
The alarm list is only half of the story. What the thresholds behind those messages are set to, why each protection carries a delay, and how the settings have to co-ordinate with the changeover device and with the site are worked through in generator control panel and protections.
The set will not crank
A no-crank is nearly always one of three things: the battery has no energy, the controller has not been given permission to start, or the starter circuit itself is open. Check them in that order, because the first two cost nothing and account for most of the calls.
Battery voltage at rest tells you little. What matters is the voltage while cranking, measured first at the battery terminals and then at the starter: a battery that reads 12.6 V at rest and 9 V under load is not the same battery as one that holds 11 V under the same load. A charger that failed quietly a month ago produces exactly this symptom, which is why the maintenance schedule asks for a monthly battery and charger check rather than an annual one.
| Check | How to test it | If it fails |
|---|---|---|
| Battery at rest, then during crank | Voltmeter across the terminals, then across the starter | Charge and load test; replace if it will not hold; repair the charger |
| Terminals and earth strap | Look for corrosion, feel for heat after cranking, measure volt drop across the joint | Clean, refit and torque to the manual |
| Charger output | Meter at the charger with the set stopped | Repair or replace; a dead charger is a very common cause |
| Control switch position | Auto or manual, and what the controller display shows | Put it in the mode the installation intends, not the mode that starts it |
| Emergency stop loop | Continuity through the loop, point by point | Find the open point; do not bridge it to get running |
| Start relay and solenoid | Audible click, then voltage at the solenoid terminal | Replace the relay or the solenoid |
| Interlocks and permits | Any remote stop, fire alarm or ATS interlock in the start path | Clear the condition, not the interlock |
It cranks but does not fire
Cranking without firing means the engine is turning and compressing but not combusting, and the list is short: fuel is not arriving, air is not arriving, or the fuel is not being ignited. Air is rarely the cause on a set that ran yesterday; fuel is the usual answer, and the shut-off solenoid is the usual place.
Start at the filter head and the fuel shut-off. A closed solenoid, a filter housing full of air after a service, a blocked filter fed from dirty fuel, a fuel cock left half open, or a priming pump not used after a filter change cover most cases. Diesel that has stood for a year can also grow the microbial contamination that blocks a filter within a few running hours, and cutting the old filter open is the only way to see it. Where the site is cold, the cold-start aid and the fuel itself belong on the list before anything mechanical.
It starts and then shuts down
A set that fires and then stops after a few seconds, or after a few minutes, is doing what it was told: a protection has operated. The controller log names it, and the timing matters. A loss of oil pressure three seconds after start is an oil, sender or wiring problem; the same reading three minutes in can be heat, dilution or a worn bearing. Read the shutdown code with the clock, not on its own.
| Shutdown | What it protects | Typical field causes | Verify before restarting |
|---|---|---|---|
| Low oil pressure | Bearings and turbocharger | Level, viscosity, blocked filter, sender or wiring, pump wear | Pressure on a master gauge against the manual figure |
| High coolant temperature | Cylinder head, liners, gaskets | Coolant loss, airlock, blocked core, thermostat, belt, fan, ambient heat | Radiator face and airflow, coolant level cold, belt tension |
| Low coolant level | The cooling system | A leak, a head gasket, a sticking level switch | The cause of the loss, not the level itself |
| Overspeed | The whole machine | Governor or actuator, wiring, fuel or oil reaching the intake | The cause, found and fixed, before any restart |
| Low fuel level or pressure | Combustion | Level, blocked filters, air in the line, lift pump | Fuel quality and filter condition, not just the level |
Two of these deserve a warning. Overspeed and low oil pressure are the shutdowns where a reset-and-retry habit breaks a machine that was still repairable, and both are worth diagnosing before the set is started again. A controller that shuts a set down is doing its job; the fault is the condition it detected, not the protection.
It runs, but the load trips
A set that runs cleanly at no load and then trips its breaker as load is applied is usually not an engine fault. The engine is doing its job and the electrical path is objecting. Separate the two by watching the panel through the transfer: if speed and frequency hold and the breaker opens, the problem is current or voltage; if the engine stumbles before the breaker opens, the problem is the engine or its fuel supply.
The usual candidates are a breaker set too low for the inrush a motor, a chiller or a UPS presents; a single-phase load placed on one line of a three-phase set; a neutral or earth connection disturbed during the installation; and an ATS that transfers faster than the engine can accept load. A set that runs perfectly on a manual test can still fail on a real outage, because the ATS only proves itself when the mains actually disappears – the difference between an ATS and an AMF panel is worth understanding before blaming the generator.
| Symptom | Likely area | Test that separates them |
|---|---|---|
| Breaker trips as load is applied | Overcurrent setting, inrush, a real fault | Read the current at the moment of trip against the breaker curve |
| Voltage collapses but recovers | AVR response, excitation, a heavy motor start | Watch voltage and current together during the start |
| Engine stumbles and black smoke | Fuel supply, governor, air filter | Load step applied manually while watching fuel pressure |
| Frequency drops and does not return | Governor, fuel rack, load above the rating | Compare the running kW against the rating for that duty and the site load list |
| Transfer happens, then the set trips | The ATS, the changeover timing, the neutral | Manual transfer, then automatic transfer, and compare |
| Only one phase is affected | Single-phasing, a fuse, a loose connection | Measure all three line currents at the same time |
Frequency and voltage that wander
Steady-state voltage and frequency are one thing and stability is another. Drift that follows the load points at a governor or an AVR responding slowly; hunting, where the reading swings in a regular rhythm, points at the controlling loop rather than at the load. Both are worth measuring with a meter, because a digital display often averages away exactly the movement that identifies the fault.
Voltage that dips when a large load starts and recovers within a moment, or frequency that drops and returns in a second, can be normal. Voltage that never recovers, or that sits above the rated value, is not. On a set feeding electronics, the AVR response and the excitation margin matter more than the no-load voltage, and it is worth checking the set before blaming the equipment downstream of it.
Overheating
Overheating is the fault where the field evidence is easiest to collect and most often skipped. A radiator core that is a third blocked by dust looks clean from the front, and a set in a container can be starved of air by the way the enclosure doors, the inlet louvers and the prevailing wind line up. The cooling system also has to reject more heat as the air the engine breathes gets hotter and thinner, which is why a hot-climate set is de-rated before it is sized rather than after it fails.
| Cause | What you will see | What to do |
|---|---|---|
| Low coolant or an airlock | Level low when cold, temperature climbs quickly under load | Find the loss, refill with the specified mix, bleed the system |
| Blocked radiator core | Temperature rises with load, normal at idle, core face hot and dusty | Clean the core from the air side, not just the grille |
| Thermostat or belt | Temperature rises fast, or the top hose stays cool | Replace, and check belt tension and condition |
| Recirculating hot air | Temperature settles above normal only inside the enclosure | Fix the airflow path and the louvers, not the engine |
| Ambient and altitude de-rate | It only happens in summer or only at site | Apply the de-rate at sizing; do not push the set past it |
| Coolant concentration | Temperature fine, then a boil, or a repeat top-up | Correct the glycol and water ratio for the site |
Smoke: black, white and blue
Exhaust colour is a cheap diagnostic and it is specific. Black smoke is unburnt fuel, too much fuel for the air available, and on a healthy set it appears briefly as load is accepted and then clears. White smoke at running temperature is usually water or unburnt fuel in the exhaust, while white smoke at start-up on a cold engine is normal. Blue smoke is lubricating oil, and it points at the turbocharger, the valve guides or the rings.
| Colour | What it means | Usual causes | Next step |
|---|---|---|---|
| Black, continuous under load | Excess fuel, or short of air | Blocked air filter, turbocharger, injector or pump, over-fuelling | Air filter and intake first, then injection |
| White, at running temperature | Water or unburnt fuel in the exhaust | Coolant reaching a cylinder, injection timing, low compression | Check for coolant loss, then the injectors |
| Blue | Lubricating oil in the exhaust | Turbo seals, valve guides, piston rings, an overfilled sump | Oil consumption and turbo shaft play |
| Grey or hazy at light load | Incomplete combustion at low load | Long periods at a small fraction of the rating | Load the set, and apply the load bank test |
Wet stacking and light-load running
A diesel that runs for months at a small fraction of its rating never reaches the temperature that burns off its deposits, and the result is the classic light-load problem: unburnt fuel and soot collecting in the exhaust, the turbocharger and the cylinders. The symptoms are smoke, oil that darkens early, rising fuel consumption and, eventually, a set that will not accept full load when it is finally asked to.
The cure is load, not an additive. A load bank test once a year, at a level the set was designed for, does what no amount of idling can do, and the maintenance schedule treats it as a service item rather than a commissioning exercise. Light-load running also shows up as fuel consumption that is worse than the datasheet promised. Where a site cannot provide the load, a resistive load bank is the tool, and running a set lightly for years is a choice with a repair bill attached.
Vibration, noise and leaks that changed
The interesting word is “changed”. A set has a signature: the noise it makes, the way it moves on its mounts, the small marks it leaves underneath. A new oil weep, a new rattle at the front of the engine, a collapsed mount or a hardened hose is cheap now and expensive later, and a weekly walk-round exists to catch exactly those changes. Noise that has moved from the machine to the enclosure, or the reverse, is covered in silent and open-frame sets. This is why the maintenance schedule asks for the same readings to be written down rather than simply looked at.
Vibration that is new, or a noise that has moved from the enclosure to the machine, is worth investigating before the next long run. Loose mountings, a failing coupling, a fan touching its shroud and an alternator bearing on its way out all announce themselves this way, and all of them are cheaper to fix before they fail than after.
What to record, and what to send us
Fault finding gets much faster when the log has been kept, because the log turns a symptom into a measurement and a change into a date. Six lines per visit are enough, and the value is in the comparison with the previous line rather than in the number itself.
| Field | Why it matters |
|---|---|
| Run hours | The only reliable trigger for every hour-based service interval |
| Load and kW during the test | Separates a real test from a no-load run, and shows light-load history |
| Battery voltage before, during and after crank | The earliest warning of a dying battery or a failed charger |
| Coolant level and condition | Catches a slow loss before it becomes a shutdown |
| Fuel level, water drained, filter dates | Fuel ages whether the set runs or not |
| Alarm history and shutdown codes | Turns a symptom into a measurement for whoever diagnoses it |
| Anything that changed since the last visit | The single most useful line in the whole log |
When you send a fault to a service desk, the useful package is short: the model and serial number, the running hours, what the set does and does not do, the shutdown code, and photographs of the panel and of the display page. That is enough to decide whether the next step is a phone call, a part or an engineer, and it avoids the most expensive sentence in generator maintenance, which is “we changed the part and it is still doing it”. The rest of our diesel generator range is described by rating and by duty.
Questions we are asked
Why does my generator start and then stop after a few minutes?
Something is protecting the machine: most often low oil pressure, high coolant temperature or a low coolant level. The controller stores the reason, so read the shutdown code before restarting. If it is oil pressure, check the level and the sender; if it is temperature, check the coolant level cold and the radiator face. A set that stops the same way twice will usually stop a third time, so diagnose it rather than resetting it.
What does the overcrank alarm mean?
The controller turned the engine for the number of attempts or the number of seconds allowed and never saw it reach running speed. It is a statement about starting, not about the engine internals: no fuel, air in the fuel, a closed shut-off, weak batteries or a cold-start problem. A set that cranks healthily and will not fire is usually a fuel-side fault, and the filter head is the place to look first.
The engine runs but the building stays dark. Where do I look?
The generator is only half of a standby system. If the set runs and the load does not transfer, the fault is usually in the changeover: a failed transfer signal, a breaker that did not close, a control fuse or an interlock. If the load transfers and then trips, look at the breaker setting and the inrush. The ATS and AMF panel is the part of the system that fails quietly between tests.
Is black smoke always a serious problem?
Not always. A brief puff of black smoke as a large load is accepted is normal on a mechanical engine, and it should clear as the governor settles. Continuous black smoke under normal load is not normal: it means excess fuel or insufficient air, and the air filter, the intake path and the turbocharger are the first things to check before the injection system is touched.
Can I reset a shutdown and keep running?
You can, but for two alarms you should not: overspeed and low oil pressure. Both can destroy an engine that is still repairable, and a reset removes the evidence. For the other shutdowns, read the code and the snapshot first. Restarting to see whether the fault repeats is a reasonable diagnostic step only when it is safe for the machine and the load, and never when the alarm was overspeed.
Why does the set overheat only in summer?
Because the set was sized on an ambient and an altitude that the site does not always have. Both reduce the mass of air the engine can breathe and the cooling system can reject, so a set that is comfortable at 25 °C can be at its limit at 48 °C. A set for a hot site should be de-rated at the sizing stage; if it is already installed, the honest answer may be a larger radiator, better airflow or accepting a lower continuous load, and this is worth discussing with us rather than with an alarm relay.
Describe the symptom, not the part
Send us what the set does, what the controller says and the running hours, and we will tell you which check to do first – and quote a part only when the evidence points at it.
Written and maintained by the KVA Grid sales engineering desk. The maintenance intervals, the load bank test and the hot-climate de-rating referred to on this page follow the figures used on our maintenance schedule page, which are typical for a diesel set in the Gulf. Alarm thresholds, protection settings and shutdown delays are the controller and engine manufacturer’s, and the manual for the specific machine governs. Ratings and performance classes are as defined in ISO 8528-1, and the temperature rise of the machine is defined in IEC 60034. This page describes general practice for buyers and operators and is not a substitute for the site manual or for a competent engineer. Reviewed 2 October 2026.