Generator noise produces more disputes than any other line on a datasheet, and almost all of them come from two numbers being confused. The regulated figure is a sound power level, the figure your neighbour hears is a sound pressure level at a distance, and the two are not interchangeable. This page sets out what each one means, the levels to expect from each enclosure, where a site limit actually comes from, and what genuinely reduces the noise.
Two numbers that get confused
Sound power is a property of the machine: the total acoustic energy it radiates, expressed as a level in dB and written as LWA or LwA. It does not depend on where you stand, and it is the figure a noise directive regulates. Sound pressure is what a meter reads at a point: it depends on distance, on the ground, on walls and on the enclosure, and it is written as dB(A) at a stated distance, most often 7 m.
The practical consequence is that a supplier can give you a legal sound power figure that tells you nothing about whether your boundary will comply, and a supplier can give you a dB(A) at 7 m that says nothing about whether the declaration of conformity is in order. A site needs both: the LWA for the compliance file, and the dB(A) at the relevant distance for the planning argument. The regulatory side is covered in our note on export certification, and the rest of this page is about the second number.
Sound pressure falls with distance
In free air, sound pressure falls by about 6 dB(A) every time the distance doubles. That single rule explains most of the confusion between two datasheets: a set quoted at 100 dB(A) at 1 m and the same set quoted at 83 dB(A) at 7 m can be the same machine, and one quoted at 65 dB(A) without a distance is a question rather than a specification.
| Distance | Level, free air | What it is good for |
|---|---|---|
| 1 m | 100 dB(A) | The figure many datasheets quote, and the one that means least on its own |
| 2 m | About 94 dB(A) | Close range, and a useful check on the arithmetic |
| 4 m | About 88 dB(A) | Working distance at a small installation |
| 7 m | About 83 dB(A) | The distance most site specifications and permits use |
| 14 m | About 77 dB(A) | A boundary on a tight urban plot |
| 28 m | About 71 dB(A) | A boundary on an industrial plot |
| 56 m | About 65 dB(A) | A nearby residential facade |
Two cautions. The rule assumes a free field, and most real sites are not: a courtyard between buildings, a wall behind the set or a hard paved compound can add 3 dB(A) or more on their own. And the rule describes a point source; a very large enclosure, or a bank of sets, behaves differently.
What the regulation covers, and what it does not
In the European Union the outdoor noise directive puts generating sets below 400 kW in the listed categories whose guaranteed sound power level has to be declared, and that declaration travels in the conformity documents rather than on the datasheet. That is a market-access requirement about the machine. It is not a site limit.
The limit that governs whether the installation is acceptable is set locally: a municipality or an environmental authority sets a permitted level at a defined place, often at the property boundary or at the nearest noise-sensitive facade, and usually with a lower figure at night. That limit is the one to design against, and it is the reason the same machine can be perfectly acceptable on an industrial plot and unacceptable in a residential compound. Ask for the permitted level, the place it is measured and the time of day, before a model is selected.
The levels to expect from each build
The enclosure, not the power band, sets the order of magnitude. The figures below are the ones we quote for each build and they are typical rather than guaranteed: the exact number moves with the engine, the fan, the alternator and the attenuation package, and the only figure worth accepting is a level for the exact model at a stated distance.
| Build | Typical level at 7 m | Where it belongs |
|---|---|---|
| Open set, indoors | About 78 to 88 dB(A) | A plant room or a remote enclosure where nobody works alongside it without hearing protection |
| Basic container build | About 68 to 78 dB(A) | Industrial plots and construction sites where the boundary is a comfortable distance away |
| Standard canopy | About 58 to 68 dB(A) | A commercial site with a boundary limit to meet and normal daytime working |
| Lined acoustic package | About 48 to 58 dB(A) | Hospitals, hotels, residential compounds and city-centre data centres, where the limit is tight and often lower at night |
These four levels are the same family, not four different machines: the engine, the alternator and the rating can be identical, and the difference is the enclosure and the exhaust. That is also why the enclosure has to be chosen after the site limit is known, not before. What a container build changes beyond the noise figure is covered in containerised generator applications.
What actually reduces the noise
Attenuation is a package, not a single part. An acoustic canopy with a critical silencer inside it will still be loud if the air path is short, if the cable entries are open, or if the exhaust bellows transmits vibration into the base. The table below is the list in the order that usually pays, from the measure with the largest effect to the one with the smallest.
| Measure | Typical effect | Its limit |
|---|---|---|
| Exhaust silencer, sized and specified for the set | The largest single reduction, because the exhaust is usually the dominant source | A silencer that is too restrictive costs back pressure, power and fuel |
| Acoustic canopy or container lining | Typically 20 to 25 dB(A) at the same distance against an open set | Lining, thickness and air path; a thin canopy with short louvres cannot do it |
| Sealing the enclosure | Several dB(A) from closing gaps that would otherwise leak noise | Ventilation and service access have to be designed, not left open |
| Attenuated air inlet and discharge path | Removes the noise that escapes through the ventilation openings | A longer path costs space and airflow, and airflow costs cooling margin |
| Vibration isolation | Stops the base and the building structure becoming a loudspeaker | Mounts age and need inspecting; rigid pipework defeats them |
| Distance, orientation and barriers | Free attenuation, and often the cheapest | Reflective walls, courtyards and prevailing wind direction all change the result |
The exhaust is usually the loudest thing
On a diesel set the exhaust is normally the dominant noise source, and it is the one most often under-specified. The silencer has to be matched to the engine, the exhaust flow and the required attenuation, and it has to be installed so that the bellows and the supports do not short-circuit the vibration isolation. A critical or residential-grade silencer on the same set can move the figure by many dB compared with an industrial one, and it is usually cheaper than adding attenuation elsewhere.
The second consequence of the exhaust is the exhaust path. A silencer pointed at a neighbouring building, or a stack that discharges at first-floor height, puts the noise where it does most damage. Whether the exhaust can be routed away, raised, or turned to face a different direction is a site question, and it is worth asking before the enclosure is ordered.
The trade-off with cooling
Every attenuation measure that works by closing or lengthening the air path also makes the set hotter, and this is the reason a quiet specification is never free. The enclosure that meets a 55 dB(A) limit at a hospital also has to reject the same engine heat through an attenuated path, and on a 48 °C site the two requirements pull in opposite directions. The airflow is not an installation detail that can be fixed later; it is the reason the acoustic build and the radiator have to be designed together.
| Requirement | What it pushes towards | What it costs |
|---|---|---|
| A tighter boundary limit | Thicker lining, a longer air path, a better silencer | Airflow, cooling margin, footprint and price |
| A higher site ambient | A larger radiator and a larger air path | Space inside the enclosure, and a larger opening to attenuate |
| A smaller footprint | A shorter air path and a tighter enclosure | Some of the attenuation, or some of the cooling margin |
| A container rather than a canopy | Room for attenuators, a longer path and a service aisle | Transport, foundation and access |
| The set placed further from the boundary | Distance doing the attenuation instead of steel | Nothing but the plot layout, which is why it is worth asking first |
Where the site is hot, the acoustic and thermal design cannot be separated; the de-rating and airflow discussion in hot and humid climates applies to every quiet build as well.
How a boundary level is actually judged
When a limit applies, it is defined with conditions attached, and two measurements of the same site can differ by several dB(A) if the conditions are not the same. This is the list worth pinning down before a set is chosen, because a specification written against the wrong conditions is a fight waiting to happen.
| Condition | Why it changes the answer |
|---|---|
| Where the level is measured | The boundary, the nearest facade and a neighbouring property are three different positions |
| Day or night | Night limits are commonly lower, and the set is often running at night because the outage is at night |
| Whether other sources are running | A background level that is already close to the limit changes what the set is allowed to add |
| The set load at the time | A set at full load is louder than the same set at half load, and the test should reflect the real duty |
| The weather and the ground | Wind direction, temperature and a hard reflective surface all move the reading |
| Whether the measurement is corrected | Some permits apply a tonal or impulsive correction, which a simple dB(A) reading does not show |
What to send in an enquiry
Four facts are enough for us to propose an enclosure rather than a range, and each one changes the answer.
- The permitted level, the position it is measured at, and whether the night figure is lower.
- The power band and the duty the set will run, including the load it must carry at night.
- The site: distance to the sensitive boundary, walls or courtyards, and the summer ambient.
- Any constraint on where the exhaust can discharge, and how much room the plot allows.
With those, the silenced enclosure, the silencer and the air path can be chosen together, and the level can be quoted for the exact model rather than for a family. Without them, the honest answer is a range, and a range is how a quiet set ends up being bought twice.
Questions we are asked
What is the difference between LWA and dB(A) at 7 m?
LWA is a sound power level: the total acoustic energy the machine radiates, independent of where you stand, and it is the figure the outdoor noise directive regulates and the declaration of conformity states. dB(A) at 7 m is a sound pressure level: what a meter reads at that distance on that site, which is what a planning or boundary limit is written against. A machine can be fully compliant on sound power and still fail a tight boundary limit, and a favourable dB(A) figure does not replace the declaration.
What noise level should I expect from a containerised generator?
A basic container build typically lands at about 68 to 78 dB(A) at 7 m, and a fully lined acoustic package at about 48 to 58 dB(A) at 7 m for the same power band. A standard canopy is about 58 to 68 dB(A), and an open set indoors about 78 to 88 dB(A). Those are planning figures; the number that matters is the one for the exact model at a stated distance, and it should be quoted rather than inferred from the family.
How much does an acoustic canopy reduce the noise?
Typically 20 to 25 dB(A) at the same measurement distance compared with the open set: a machine declared at about 100 dB(A) at 1 m in the open is commonly quoted at 75 to 85 dB(A) at 1 m in a standard canopy. Above that, attenuation has to come from the silencer grade, the length of the air path and the thickness of the lining, and each of those costs airflow and space.
Is a silent canopy enough for a hotel or a hospital?
It depends on the permitted level and the distance, not on the label. A canopy that meets a commercial boundary at 30 m may still be too loud for a hospital ward window at 12 m with a lower night limit. Those sites usually need the lined acoustic package, a residential-grade silencer and a considered exhaust direction, and they need the level quoted for the exact model. The enclosure type follows from the limit; it is not the other way round.
How is generator noise measured at a site boundary?
A meter is placed at the position the permit defines – often the boundary or the nearest noise-sensitive facade – with the set running at the load the permit or the test method requires, and with the background level recorded so it can be allowed for. Day and night limits are usually different, the weather and the ground cover affect the reading, and some permits apply a correction for tones or impulsiveness that a plain dB(A) number does not show. The permit’s own conditions define the method, so read them before agreeing a test.
Can I add attenuation later if the set turns out to be too loud?
Some of it, and usually at a higher cost than doing it at the factory. A better silencer, additional lining and sealed access panels can be retrofitted, and moving the set or screening it with a barrier can be done on site. What is difficult to change later is the air path: an enclosure built with short louvres and no room for attenuators cannot be made quiet without rebuilding it, which is why the acoustic and thermal design belongs in the order rather than in the complaint.
Send the limit, the distance and the site
Tell us the permitted level, where it is measured, the load the set must carry and how much room you have, and we will quote the enclosure, the silencer and the air path together – with the level for the exact model.
Written and maintained by the KVA Grid sales engineering desk. The enclosure levels quoted here are the planning figures used across this site: open set indoors about 78 to 88 dB(A) at 7 m, a basic container build about 68 to 78 dB(A), a standard canopy about 58 to 68 dB(A) and a lined acoustic package about 48 to 58 dB(A), with a canopy typically removing 20 to 25 dB(A) against an open set. The regulatory reference is Directive 2000/14/EC, under which power generators below 400 kW are in the listed categories and a guaranteed sound power level is declared in the conformity documents; the difference between that declaration and a level at a distance is explained in export certification, and the choice between enclosure types in silent and open frame sets. Site limits, measurement positions and corrections are set locally by the competent authority and govern; this page is a guide for buyers and not a noise assessment or legal advice. Reviewed 2 October 2026.