kVA vs kW in a diesel generator: what the difference means for sizing

kW is the power the load actually uses; kVA is the apparent power the alternator has to supply. The two are tied together by the power factor: kW = kVA × power factor. A 500 kVA set rated at 0.8 power factor delivers 400 kW — but only 350 kW when the site load sits at 0.7 power factor.

Two ratings on one machine, for two different reasons

Every diesel generator set carries two ratings, and they exist because two different parts of the machine set the limit:

  • kVA is the alternator rating. The alternator limit is heat in its windings, and that heat comes from current. Current follows the apparent power, whether or not the load is doing useful work with it, so the alternator is rated in kVA.
  • kW is the engine rating. The engine limit is the shaft power it can deliver continuously at a declared ambient temperature, so the useful electrical output is what the shaft can produce after the alternator and cooling losses.

The power factor of the load is the bridge between the two figures. That is why a set is quoted as, for example, 500 kVA / 400 kW at 0.8 power factor: both numbers describe the same machine, seen from the alternator side and from the engine side. A standby set and a prime set of the same kVA are not the same machine either, which is covered in prime vs standby power.

The conversion, and the table you can read straight off

kW = kVA × power factor  ·  kVA = kW ÷ power factor

Standard set sizes converted from kVA to kW at four power factors. 0.8 is the reference power factor of a generator set; read the column that matches your load.
Set rating At 0.70 PF At 0.80 PF At 0.90 PF At 1.00 PF
20 kVA 14 kW 16 kW 18 kW 20 kW
50 kVA 35 kW 40 kW 45 kW 50 kW
100 kVA 70 kW 80 kW 90 kW 100 kW
200 kVA 140 kW 160 kW 180 kW 200 kW
250 kVA 175 kW 200 kW 225 kW 250 kW
300 kVA 210 kW 240 kW 270 kW 300 kW
400 kVA 280 kW 320 kW 360 kW 400 kW
500 kVA 350 kW 400 kW 450 kW 500 kW
800 kVA 560 kW 640 kW 720 kW 800 kW
1000 kVA 700 kW 800 kW 900 kW 1000 kW
2000 kVA 1400 kW 1600 kW 1800 kW 2000 kW

Two readings of the same table are worth keeping apart:

  • Working up from the load: 400 kW needs 500 kVA at 0.8 PF, and 444 kVA at 0.9 PF.
  • Working down from a machine: a 500 kVA set gives 400 kW at 0.8 PF and 350 kW at 0.7 PF, and would give 450 kW at 0.9 PF if the engine is built for that output — which is the point of the next section.

The kW to kVA step inside a full sizing calculation, including the starting demand of the largest motor, is worked through in how to size a diesel generator.

Which limit is reached first

At exactly 0.8 power factor the two limits are aligned, so the set delivers its full kW rating at its full kVA rating. Move the power factor away from 0.8 and one of the two limits binds earlier than the other.

The same 500 kVA / 400 kW set on four loads of different power factor. The ceiling moves because a different part of the machine reaches its limit.
Load power factor Load at full kVA Limit reached first What the set can actually deliver
0.70 350 kW at 500 kVA Alternator current and heat 350 kW — the engine still has margin it cannot use
0.80 400 kW at 500 kVA Both together 400 kW at 500 kVA, the rated condition
0.90 450 kW at 500 kVA Engine shaft power 400 kW, so about 444 kVA of the alternator is used
1.00 500 kW at 500 kVA Engine shaft power 400 kW, with the alternator running well below its kVA rating

There is a second layer under that table: the engine figure on the datasheet is mechanical output at the shaft, and the alternator converts it to electrical power at an efficiency of roughly 94 to 96 %. Delivering 400 kW electrically therefore draws somewhere near 420 to 425 kW from the engine, which is why the engine column on a real datasheet reads higher than the kW rating of the set. The set rating already accounts for it; the point is that the two figures are not the same quantity and are never added together.

The practical consequence is simple. A site whose load sits below 0.8 power factor is buying alternator capacity it cannot use, so the power factor belongs in the enquiry next to the kW total. A site whose load sits above 0.8 power factor may reach the engine rating before the alternator looks busy, and the kW figure is then the one to watch on the control panel.

What 0.8 power factor does not mean

A 500 kVA set that delivers 400 kW is not losing 100 kW to heat. The 20 % that does not appear as kW is the magnetising and reactive component of the current, which circulates rather than being converted; the real loss in the machine is the alternator and cooling loss of a few per cent described above. That distinction matters twice:

  • On the set, because the kVA figure sets the current the alternator has to carry, whatever the load does with it.
  • On the electricity bill, where a utility that charges maximum demand in kVA is billing the same apparent power. Power factor correction equipment then pays back on the bill as well as on the generator.

Leading power factor is the opposite trap: an installation that has been over-corrected with capacitors, or a large UPS lightly loaded behind its input filter, can present a capacitive load that makes the alternator voltage regulation unstable. It is worth naming in the specification so that the alternator and the excitation system are chosen for it rather than discovered on site.

Where kVA and kW appear in a load list

Mixed load lists quote different items in different units, and the difference is not decorative:

How common loads reach the enquiry, and what has to happen before they can be added up.
Load Usually quoted in Before it is added to the total
Motor kW on the nameplate, which is shaft output Convert with the motor efficiency and power factor, not from the kW figure alone; then add its starting demand
UPS kVA and kW separately Use the kW figure for the load and check the input current, which is set by the kVA
Lighting, heaters, resistive loads kW Power factor close to 1, so kW and kVA are almost the same number
Switchgear and cable schedules Amps kVA = 1.732 × volts × amps ÷ 1000; at 400 V three-phase, 1000 A is about 693 kVA

Adding a kW figure to a kVA figure is the most common arithmetic mistake in a load list: they are different quantities, and the result of mixing them is a total that cannot be checked against anything else. Convert everything to kVA at the site power factor first, and keep the kW total separately for the engine rating.

Reading the difference on site

  • Ammeter and voltmeter give apparent power: kVA = 1.732 × volts × amps ÷ 1000 on a three-phase supply.
  • A kW meter gives the real power the load is taking at that moment, so the ratio between the two readings is the running power factor.
  • A kWh meter gives energy over time, which is a third quantity again: kW × hours. Diesel consumption is quoted per kWh at a given load, so fuel planning follows the kW figure, not the kVA.

The same range written both ways

Because the reference power factor is fixed at 0.8, the sizes in the catalogue can be read either way:

Set sizes in the KVA Grid range at the 0.8 reference power factor. The kW figures are electrical output at that power factor; the engine rating on the datasheet is higher.
Rating kW at 0.8 PF Typical application
100 kVA 80 kW Small workshop, telecom site, retail unit
200 kVA 160 kW Clinic, small hotel, light industrial
300 kVA 240 kW Supermarket, guesthouse, water pumping
500 kVA 400 kW Hospital essential block, mid-size plant, hotel
800 kVA 640 kW Industrial plant, production line, large hotel
1000 kVA 800 kW Data centre, factory, district cooling plant
2000 kVA 1600 kW Large plant, or two sets in parallel for redundancy

How the rating is then applied to a specific building is the same exercise as in how to size a generator for a hospital, and the full range is on the diesel generator sets page.

Mistakes that cost money

  • Reading 500 kVA as 500 kW. It is 400 kW at the reference power factor, and less on a poorer load.
  • Adding kW and kVA in one column. Convert everything to one unit at one power factor before the total is used.
  • Sizing on the running load only. The starting demand of the largest motor is a kVA demand and can exceed the steady-state load several times over, as the worked example in the sizing guide shows.
  • Ignoring a low power factor load. A large motor bank or an older UPS shifts the whole site below 0.8 and quietly shrinks the kW available from the set that was ordered.
  • Treating kWh as kW. Energy and power are different quantities; fuel and battery autonomy are planned on energy, the set rating on power.

Questions

How many kW is a 500 kVA generator?

400 kW at the 0.8 power factor that generator sets are rated at. The same set gives 350 kW on a load at 0.7 power factor, and 450 kW on a load at 0.9 power factor if the engine is built for that output. 500 kVA is the alternator rating; 400 kW is the electrical output at the reference power factor.

Is kVA always larger than kW?

Yes, except at a power factor of exactly 1, where the two are equal. Power factor is kW divided by kVA, so it cannot exceed 1 on an ordinary lagging load; a purely resistive load such as a heater sits at 1.0 and the two numbers coincide. Any load with motors, transformers or rectifiers sits below 1, so the kVA figure is the larger of the two.

Why is the alternator rated in kVA but the engine in kW?

Because they reach their limits for different reasons. The alternator temperature rise is produced by current, which follows apparent power, so its rating is expressed in kVA whatever the load does with the power. The engine limit is mechanical shaft power, so it is rated in kW. The published set rating, such as 500 kVA / 400 kW at 0.8 power factor, is the point where the two are matched.

Which power factor should I use in the calculation?

0.8 is the safe assumption for a mixed commercial or industrial site, and it is the reference power factor of the set itself. A site dominated by drives, LED lighting and rectifiers often sits nearer 0.9; a site with a large motor bank or a legacy UPS can sit below 0.75, and then the alternator has to be checked for current rather than for kW alone. If the real figure is not known, quote 0.8 and say so.

Does 0.8 power factor mean the set wastes 20 %?

No. The 20 % is the reactive component of the current, not heat: it is current the alternator carries without converting it into useful output. The real losses in the machine are the alternator and cooling losses, of the order of 4 to 6 %, and they are already inside the set rating. What the power factor does change is how much kW can be taken out of a given kVA.

What to send for a quotation

Send the load list with the running kW of each group, the power factor if the site has already been measured, the starting method of the largest motor, the supply voltage and frequency, and the duty the set has to carry. The kW figure sets the engine, the kVA figure sets the alternator, and between them they decide the rating that comes back.

Send the load list and get a rating back

We answer with the kVA, the engine rating, the enclosure and the fuel autonomy — in writing, usually the same working day.

Request a quote WhatsApp the sales desk

Written and maintained by the KVA Grid sales engineering desk. Conversion figures are exact at the stated power factors; efficiency and engine figures are typical values, and every set is quoted against its own datasheet. Figures are for 400/230 V, 50 Hz, three-phase sets unless stated. Reviewed 30 September 2026.